Dollar coin We raised $14M to build the planning engine for AEC.
Read more
Free trial

IBC Steel Construction: AISC 360 Reference and Structural Requirements — Chapter 22

June 7, 2026 · 6 min read

TL;DR — Key Takeaways

IBC Chapter 22 adopts AISC 360 (Specification for Structural Steel Buildings) as the primary steel design standard, with AISC 341 (Seismic Provisions) required for buildings in SDC B and higher.

Two design methods are available under AISC 360: LRFD (Load and Resistance Factor Design) and ASD (Allowable Strength Design) — both are fully supported and the designer may choose either.

Seismic systems for steel include: special moment frames (SMF), intermediate moment frames (IMF), ordinary moment frames (OMF), special concentrically braced frames (SCBF), eccentric braced frames (EBF), and special plate shear walls (SPSW) — each with different ductility demands and SDC applicability.

Special moment frames (SDC D–F) require prequalified or tested connections per AISC 358 or FEMA 350/351 — not standard bolted shear-tab connections.

High-strength bolts (A325, A490, ASTM F3125) require special inspection for snug-tight vs pretensioned vs slip-critical conditions per §1705.2.

Cold-formed steel framing (light gauge) is governed by AISI S100 referenced in IBC §2210, not by AISC 360 — these are distinct standards.

Fireproofing of structural steel (spray-applied fireproofing or intumescent coating) is required per IBC Table 601 fire resistance ratings for the applicable construction type.

The IBC Steel Standards Framework

IBC §2205.1 states: "The design of structural steel shall be in accordance with AISC 360."

For buildings in SDC B through F, IBC §2205.2 adds: "The design of seismic-force-resisting systems of structural steel shall be in accordance with AISC 341."

A third standard — AISC 358 (Prequalified Connections for Special and Intermediate Steel Moment Frames) — governs the specific connection designs used in special moment frames.

Additionally:

• AISC 303 — Code of Standard Practice (industry norms for fabrication and erection)

• AWS D1.1 — Structural Welding Code, adopted by IBC §2204.1 for welded connections

• ASTM material specifications — A36, A992, A500, A53 for different steel products

IBC structural design Chapter 16

Steel Design Methods (AISC 360)

LRFD — Load and Resistance Factor Design

LRFD applies factored loads (φRn ≥ ΣγiQi) where:

• φ = resistance factor (typically 0.90 for flexure, 0.75 for fracture/bolts)

• Rn = nominal strength

• γi = load factors (1.2 for dead, 1.6 for live, etc.)

• Qi = load effect

LRFD is the default method for most structural steel design and produces more efficient designs for members controlled by live load.

ASD — Allowable Strength Design

ASD compares service loads against allowable stresses (Ra ≤ Rn/Ω) where Ω is the safety factor (1.67 for flexure, 2.00 for fracture/bolts). ASD remains widely used and is preferred by some practitioners for its intuitive interpretation of safety.

Both methods produce equivalent designs when applied correctly. The choice is the structural engineer's prerogative.

Common Steel Material Specifications

ASTM StandardProductFy (yield strength)Common Use
A992W-shapes (wide flange beams)50 ksi minimumColumns, beams, primary framing
A36Plates, angles, channels36 ksiConnection plates, lintels, miscellaneous steel
A500 Gr. BHSS rectangular/square46 ksiColumns, struts, braces
A500 Gr. BHSS round (tube)42 ksiColumns, architecturally exposed
A53 Gr. BPipe (structural)35 ksiLight columns, handrails
A490 (F3125 Grade F)High-strength bolts130 ksi tensileHigh-strength connections
A325 (F3125 Grade A)High-strength bolts92 ksi tensileStandard high-strength connections

A992 W-shapes are required for all W-shapes used in seismic-force-resisting frames per AISC 341 — the Fy/Fu ratio is controlled to ensure ductile yielding before fracture.

Seismic Steel Systems (AISC 341)

System Selection by SDC

Seismic SystemSDC ApplicabilityR FactorHeight Limit
Ordinary Moment Frame (OMF)A, B, (C with limits)3.5Limited in SDC D+
Intermediate Moment Frame (IMF)A, B, C, D (limited)4.535 ft in SDC D
Special Moment Frame (SMF)All SDC8.0No limit
Ordinary Concentrically Braced Frame (OCBF)A, B, C3.2535 ft in SDC D
Special Concentrically Braced Frame (SCBF)All SDC6.0No limit
Eccentric Braced Frame (EBF)All SDC8.0No limit
Special Plate Shear Wall (SPSW)All SDC7.0No limit

(R = response modification factor; higher R = greater ductility assumed = lower design seismic force)

Special Moment Frames (SMF) — Critical Requirements

SMFs are the most ductile and commonly used lateral system for mid-rise and high-rise steel buildings in SDC D–F. Key requirements under AISC 341:

Beam-column connections must be prequalified or tested:

AISC 341 requires that SMF connections demonstrate the ability to achieve 0.04 radian interstory drift capacity through either:

• Prequalified connection designs per AISC 358 (reduced beam section/RBS, bolted end plate, bolted flange plate, etc.), OR

• Project-specific connection testing per AISC 341 Appendix S

The reduced beam section (RBS or "dog-bone") connection — which reduces the beam flange width at a set distance from the column face — is the most common prequalified SMF connection for welded moment frames.

Panel zone requirements:

The column web panel zone must be checked for shear capacity — panel zone yielding is a designed ductile mechanism but must be controlled. Doubler plates may be required where the panel zone is insufficient.

Continuity plates (column stiffeners):

Transverse stiffeners (continuity plates) are required at the beam flange locations in the column to transfer flange forces into the column web.

Fireproofing of Structural Steel

Structural steel is non-combustible but loses strength rapidly at elevated temperatures (above 600°F) and must be fireproofed to achieve the required fire resistance ratings per IBC Table 601.

Methods of fireproofing:

Spray-Applied Fire Resistive Materials (SFRM / "spray-on fireproofing"): The most common — mineral fiber, cementitious, or intumescent materials sprayed directly onto steel surfaces. Rated assemblies are published in UL Fire Resistance Directory.

Intumescent coatings: Paint-like materials that expand under heat to form an insulating char. Required for architecturally exposed structural steel (AESS) where spray-on would be unacceptable visually.

Concrete or masonry encasement: Used in pre-1970s construction; rarely used today.

Membrane ceiling systems: The fire resistance may come from the floor/ceiling assembly rather than the beam — the ceiling membrane provides the required rating.

IBC fire-resistant construction Chapter 7

Special Inspections for Steel (§1705.2)

IBC §1705.2 requires special inspection for structural steel:

Welding: Continuous inspection during all complete joint penetration (CJP) and partial joint penetration (PJP) welds in the primary load path. Fillet welds require periodic inspection.

High-strength bolt installation: Periodic inspection for snug-tight bolts; continuous inspection for pretensioned and slip-critical connections per AISC Research Council on Structural Connections (RCSC).

Seismic systems: Continuous inspection for all connections in seismic-force-resisting frames (SMF, SCBF, EBF, etc.)

The special inspector must be a certified welding inspector (CWI per AWS QC1 or equivalent) for weld inspection.

Research Steel Construction Requirements for Your Project

Steel seismic system selection, connection design, and fireproofing requirements depend on your SDC, occupancy, and construction type. Melt Code lets you search IBC Chapter 22, AISC 360/341 references, and your jurisdiction's amendments together.

Search structural steel requirements on Melt Code Try Melt Code →

Frequently Asked Questions

Q: Does AISC 360 or IBC govern steel design?

IBC Chapter 22 adopts AISC 360 by reference. AISC 360 governs design calculations. IBC Chapter 22 adds supplemental requirements, particularly for seismic design (requiring AISC 341 for SDC B and higher).

Q: When is AISC 341 required?

IBC §2205.2 requires AISC 341 (Seismic Provisions for Structural Steel Buildings) for any building in SDC B or higher that uses structural steel in the seismic-force-resisting system. SDC A buildings may use AISC 360 alone.

Q: Can I use standard bolted shear tab connections in a special moment frame?

No. AISC 341 requires that SMF connections be prequalified per AISC 358 or project-tested — standard shear tab connections are not pre-qualified for moment frame applications. Moment frames require full moment connections at the beam-to-column joint.

Q: What is architecturally exposed structural steel (AESS)?

AESS is steel that is visible in the finished building — exposed to view as an aesthetic element. AISC 303 Section 10 defines AESS categories with increasing requirements for surface finish, weld appearance, and dimensional tolerances. Fireproofing for AESS typically uses intumescent coatings rather than spray-on materials.

References

1. International Code Council — IBC 2024, Chapter 22: Steel

https://codes.iccsafe.org/content/IBC2024P1/chapter-22-steel

2. AISC — AISC 360-22: Specification for Structural Steel Buildings

https://www.aisc.org/globalassets/aisc/publications/standards/a360-22-spec-for-structural-steel-buildings.pdf

3. AISC — AISC 341-22: Seismic Provisions for Structural Steel Buildings

https://www.aisc.org/globalassets/aisc/publications/standards/aisc-341-22.pdf

4. AISC — AISC 358-22: Prequalified Connections for Special and Intermediate Steel Moment Frames

https://www.aisc.org

5. AWS — AWS D1.1/D1.1M: Structural Welding Code — Steel

https://www.aws.org/standards/page/d1-structural-welding-codes

6. UpCodes — IBC 2024 Chapter 22 (searchable text)

https://up.codes/viewer/california/ibc-2024/chapter/22/steel

Have a code question? N/A
Try Melt Code →