Takeoff & Estimating — Mechanical (HVAC)

Fan Coil Unit (FCU)

A small room unit with a fan and a water coil that heats or cools its space.

Quick Answer

A fan coil unit (FCU) is a compact terminal unit with a fan and a coil fed by hot or chilled water, used to heat or cool the room it sits in. A two-pipe unit has one water supply and return loop, a four-pipe unit has separate heating and cooling loops. Estimators count FCUs each (EA) by size.

The Full Picture

A fan coil unit moves room air across a water coil. Chilled water makes it a cooler, hot water makes it a heater, and a thermostat controls the fan speed and a control valve. One university design guideline describes FCUs as relatively small, unducted, floor or ceiling mounted units used for cooling and/or heating the room in which they are located, and separates them from ducted blower coil units. They suit buildings with many small rooms that need individual control, where a central plant supplies the water.

The two-pipe versus four-pipe distinction changes what is counted. A two-pipe unit has one supply and one return connection on a single water loop, which carries either hot or chilled water depending on the season. A four-pipe unit has a chilled-water supply and return and a hot-water supply and return, so it can heat or cool at any time. Four-pipe units cost more and need more piping, valves and control hardware. The same university guideline calls for every unit to be individually scheduled and identified on the drawings, and it asks for a drain pan, a removable filter and insulated cold piping. Those features can show up as separate line items.

On the plans, FCUs are tagged on the mechanical floor plan, with piping runs shown to the unit. The equipment schedule lists the tag, type (floor, horizontal, recessed or concealed), CFM, cooling and heating capacity, coil connection size, motor data and the control arrangement. The takeoff unit is each (EA) by tag and size. The piping to each unit, valves, strainers, drain lines, power and thermostat are measured or counted separately by the mechanical and electrical trades.

Pricing slips include counting units by symbol while the schedule lists a different type, missing that some units are four-pipe and others two-pipe, and leaving out the drain or the control valve package. Another is the ceiling or wall opening: recessed units need a framed opening and access, which falls between the mechanical, framing and drywall scopes. Ventilation air is often supplied separately, and the guideline notes that units should not have an integral outside air connection where separate minimum ventilation air is provided so the ductwork for it is a different line.

Real Examples

→Worked takeoff: units by size and piping: A five-floor residence has 8 FCU-1 (400 CFM) and 4 FCU-2 (600 CFM) on each floor. The count is 5 x 8 = 40 EA of FCU-1 and 5 x 4 = 20 EA of FCU-2, which is 60 EA in total. If the schedule marks all as four-pipe, there are 60 x 4 = 240 water connections to price. If it were two-pipe, the same 60 units would have 60 x 2 = 120 connections.
→Mixed schedule: A hotel schedule lists guestroom units as four-pipe and corridor units as two-pipe. The estimator splits the counts by type before pricing, because the valves, control package and piping differ even though both are called FCUs.
→Recessed units and the ceiling: Six recessed horizontal FCUs sit above a drywall ceiling and need access panels. The estimator checks that the access panels are carried by someone, and that the framing of the opening is in the framing or drywall scope and not assumed to be mechanical.

Common Misconceptions

People assume: A fan coil unit is the same as an air handling unit.

Actually: An FCU is a small unit that serves the room it sits in, while an AHU is a large central unit serving many spaces through ducts. The university guideline distinguishes FCUs from ducted blower coil units as well.

People assume: Two-pipe and four-pipe FCUs are priced alike.

Actually: A four-pipe unit has separate heating and cooling connections, additional valves and a more complex control package. The difference shows up in the unit, the piping and the controls.

Does MeltPlan Solve This?

Partially — adjacent

Counting fan coil units by tag and size from the mechanical plans is a takeoff task, and MeltPlan's takeoff service has AI pull quantities from plans with US-based experienced estimators reviewing and adjusting them. Confirming two-pipe or four-pipe against the schedule, and pricing the piping, controls and access, stays with your estimating team.

Get FCU counts pulled from your plans →

Frequently Asked Questions

What is a fan coil unit?

A small unit with a fan and a coil that gets hot or chilled water from a central plant and heats or cools one room. A university guideline defines them as small, unducted units that serve the room they are in.

What is the difference between 2-pipe and 4-pipe?

A two-pipe unit has one supply and one return on a single loop, carrying hot or chilled water. A four-pipe unit has separate chilled and hot water loops, so it can heat or cool at any time.

How is an FCU counted in a takeoff?

Each (EA) by tag and size, with the type (floor, horizontal, recessed) noted. Piping, valves, drains, power and thermostats are separate quantities.

Where is the FCU shown on drawings?

It is tagged on the mechanical floor plan and listed on the equipment schedule with its CFM and capacities. Specifications are in Division 23.

What is the difference between an FCU and a blower coil unit?

In the university guideline, an FCU is unducted and serves its own room, and a blower coil unit is ducted and may serve adjacent areas. Both are counted EA, but ducting changes the scope.

Related Terms

More Takeoff & Estimating — Mechanical (HVAC) Terms

Sources

  1. University of Michigan Design Guideline 230015: Fan Coil Units and Blower Coil Units
  2. Duke University Construction Standards: 23 70 00 Central HVAC Equipment (Air Handling Units)
  3. U.S. DOE: Guide to Home Heating and Cooling